Refrigeration Past, Present and Future // W.9.5

No one has a crystal ball to predict the future but considering history and current needs of the market allow some predictions with reasonable certainty.

Past

Cooling with ice has been around for thousands of years and the Romans, known to bring ice and snow from the Alps to cool their wine, gave us the term “refrigeration” from the word frigor-coldness.

It is easy to forget that the basic term we use daily for description of load is the “ton” which is the amount of heat needed to melt or freeze one ton of water in 24 hours. This translates into 12,000 Btu/hr or 144 Btu per pound. Modern texts and calculations use metric units such as kiloJoules per kilogram, but some of the pioneering work in thermodynamics was done in England and Scotland in the 18th century and the British Thermal Unit (BTU or Btu) was used frequently by 1870. Our basic process of vapor compression refrigeration is often credited to an American physician, John Gorrie, who was granted U.S. patent 8080 in 1851. Interestingly, his design used air as a primary refrigerant and merely compressed and re-expanded it without changing its state from liquid to gas.

Other pioneers in the field of modern style phase change refrigeration are Ferdinand Carré of France, and Americans Jacob Perkins and Oliver Evans. By the end of the 19th century, vapor compression, mechanical refrigeration was in common industrial use for ice production and food processing.

Early systems used materials not often found in modern systems, such as sulfur dioxide, ether and methyl chloride, which proved to be toxic, explosive, or both. Surprisingly, some of the earliest systems used Carbon Dioxide (CO2) and Ammonia, which seem to have been “rediscovered” in recent years for their efficiency and lack of ozone depletion potential.

Although specialty cooling methods, like Peltier-thermoelectric and vortex tubes, have been around for many decades, efficiencies and scalability limit their use.

Present

Most systems used today are based on compression of a cool low pressure vapor into a hot, high pressure vapor. This hot vapor is condensed into a liquid by removing heat in a heat exchanger called a condenser. The resultant liquid is allowed to expand into a vapor by dropping its pressure. This expanding liquid-vapor mix is admitted to another heat exchanger, the evaporator, which provides cooling by absorbing the heat from the space or other fluid. See Figure 1.

Figure 1 - Basic Refrigeration System
Figure 1 - Basic Refrigeration System Liquid

It is likely that for the near term, perhaps 10 to 15 years, vapor compression refrigeration will continue to be the standard means of providing cooling. Advances will be incremental, rather than any revolutionary new technology being discovered or adopted.

Current needs of the market are really based on two factors: energy conservation and environmental effect. Of course, both are related and improvements in one can lead to improvements in the other. According to average U.S.EPA eGRID data, every kilowatt generated also generates 1.3 pounds of CO2 emissions, so energy efficiency has a direct effect on global warming potential.

Currently, to build electrical power plants cost over $2,100 per kW generated for fossil fuel and between $3,000 and $4,000 per kW for nuclear power generation. It may take more than a decade for a new plant to come on line, and political pressures concerning the environmental effects of fossil fuel burning and nuclear waste may increase time and costs significantly. Utilities may be unwilling or unable to commit the $2+ billion needed to capitalize new plants, particularly in the present economic climate.

The present and short term alternative is conservation of existing resources to slow the need for new generating capacity. Almost every utility will grant rebates or incentives to customers who show energy savings. For residential customers who switch to more efficient CFL compact fluorescent lighting, the rebate may be 100s of dollars, for industrial and commercial customers, the rebates may amount to 100s of thousands of dollars. Almost all parts of a refrigeration system can be made more efficient with new products and technologies, and many will qualify for these incentives.

Compressors
Compressor technology continues to make some improvements in efficiency with better materials, and moderate design changes, but probably the best means of conservation will involve changes in refrigerants and adoption of variable speed drives. Natural refrigerants like carbon dioxide, ammonia and propane can be used to ameliorate the environmental impact of the inevitable loss of system refrigerant. In some applications, these replacement refrigerants save energy as well. Possibly the best avenue for savings in any motor driven device will be variable speed technology. Slowing the speed of a compressor will yield very high savings in terms of input power required. Since most systems do not run at full load very often, the savings can be significant. Some manufacturers quote up to 40% energy savings for variable speed compressors. Lubrication concerns have limited the use of variable speed drives on compressors in the past, but newer compressors have been designed with speed control in mind.

Condensers
Often ignored in plans to save energy, particularly in supermarket refrigeration systems, are the condenser fans and pumps. The Fan Affinity Laws state that air or water volume delivered by a fan or pump is directly proportional to the fan or impeller speed. However, the power used by the fan or pump varies as the cube (X3) of the speed. In essence, dropping the speed by half will decrease power used by a factor of 8.

Based on design conditions, a majority of systems run a majority of the time at reduced speed and load. Figure 2 illustrates the run-time versus load data, which is fairly consistent for all geographical areas.

Figure 2 - Run Time vs. Load
Figure 2 - Run Time vs. Load

A typical air cooled condenser on a supermarket may use 75,200 kW per year and there may be 4 such units on each store. The power used, just for fans, on each store can amount to over 300,000 kW per year. Variable Frequency Drive (VFD) fan controls have been shown to save 50%+ of this energy and, in this instance, would prevent 195 tons of CO2 emissions.

The benefits and energy savings accruing from the use of VFDs on condenser fans is well proven and supported by utilities in the form of rebates and incentives. However, most refrigeration mechanics rarely need to program VFDs, or may not be familiar with them. Most VFDs in the market have hundreds of parameters that must be set, or at least investigated. A solution that offers a completely programmed, wired and tested plug-andplay VFD fan controls can deliver the energy savings and rebate potential, while not requiring excessive time, effort and cost on the part of the installer.

Figure 3 - “Plug-and-play” VFD Fan Control
Figure 3 - “Plug-and-play” VFD Fan Control

Evaporators
The work to be done in any refrigeration system is realized in the evaporator but the technology to increase the efficiency of the evaporator has lagged behind the improvements to the compressor and condenser. The last large increase in the evaporator efficiency probably occurred when the change to HCFC and HFC refrigerants caused a redesign of tube sizes and refrigerant flow. At about the same time, the wide application of floating head pressure and floating suction pressure began. The energy savings from lower head pressures and higher suction pressures are easily quantifiable, but may lead to consequences in system performance. Traditional TEVs (thermostatic expansion valves) lose stability and control of superheat when the pressure drop across the valve port changes significantly.

Thankfully, balanced port designs allowed mechanical TEVs to be more stable over wider load and pressure drop ranges. However, trying to maximize system efficiency by minimizing valve pressure drop was limited even for balanced port styles. Electronically controlled expansion valves, EEVs, which had been used successfully in large chiller systems, began to be used in smaller refrigeration systems, to great advantage.

Although the EEV helps reach the next level of energy savings in systems by way of stable superheat control over a wide range of operating conditions, another system characteristic was slow to be addressed successfully. The very nature of refrigeration systems requires that much of the time evaporator surfaces be colder than the freezing point of water. The resultant frost is typically regarded as a necessary evil in the process of cooling. In higher temperature systems, simple off time will suffice for defrosting the coil, but in colder applications more active means must be used. Traditional means of ridding the coil of frost have involved adding significant amounts of heat; either direct electrical resistance heat, or compressor driven hot gas. Adding additional heat to a refrigerated space to melt and discard ice already paid for in compressor run time makes no sense. The goal should be to minimize the total system energy needed to cool a product or process.

Figure 4 - Timeclock vs. Proactive Defrost Control
Figure 4 - Timeclock vs. Proactive Defrost Control

A novel idea, being used in a few controllers, “reclaims” the potential of the frost to do work. No change is made to the first part of the cycle, the compressor runs and frost will form if the evaporator surface is cold enough. Most systems continue to run the compressor until room temperature is fully satisfied. The more modern method is to cycle the compressor off for extended periods of time while allowing the fans to blow room air across the icy coil. The frost sublimates and chills the room without adding compressor run time. The advantages are direct and indirect.

Direct energy savings result from reduced compressor run time. Indirect savings are garnered by using the latent heat of the ice to absorb more heat from the space. A further indirect, and perhaps not obvious savings, is that since the frost is “consumed”, or used, during the refrigeration cycle, there is little remaining ice to be melted and removed during the defrost cycle. This allows the defrosts to be shorter, cooler and less often. Since most defrosts require hundreds or thousands of kilowatts, and three times as many Btus are added to the room, even having one fewer defrost can provide large energy savings. In the real world, some of these controllers are able to reduce the number of defrosts from the 3 per day, typical with a time clock scheduled defrost, to 3 per week. The conserved energy typically can pay for the full installation costs in 1 ó years or less, in some instances, in months. Of course, once paid for, the controllers will continue to save energy for the life of the equipment. 

Communication
Given the limitation of bringing new power plants on line, the Government and Industry are designing and implementing “Smart Grid” technology. There are many aspects to this plan, but of primary importance to the refrigeration and air conditioning industry is “Demand Response.” Demand Response allows utilities to apportion energy based on usage, cost and location. Another aspect is Advanced Metering Infrastructure (AMI). According to the DOE, AMI is an approach to integrating consumers based upon the development of open standards. Traditional communications in the HVAC&R industry have been based on proprietary, non-interoperable communication protocols. The hundreds, if not thousands, of proprietary protocols make free exchange of information on a nation-wide network impossible. While standards like BACnet and Modbus have been used in the HVAC&R industry, communication with other industries has been problematic.

The Internet is showing how all devices can be made to communicate to all other devices on a worldwide network with a minimum of intervention and integration. Refrigeration is another node on the network, and products based on TCP/IP communication are replacing many proprietary protocols now used. A new generation of system components are being planned to use, or are already using, TCP/IP to interface with other parts of the system, other systems, or even the power grid. See Figure 5.

Figure 5 - Sample of data from a controller accessed via the internet
Figure 5 - Sample of data from a controller accessed via the internet

Again, the benefits may be direct or indirect. By being able to exchange information within an individual system, the components can arrive at the most efficient combination of compressor run time, defrost scheduling, head pressure and suction pressure. Combined into a local network, these systems can exchange data to minimize energy use in the entire installation. Taken a step further, installations connected to a smart grid, can be integrated to even out demand, limit the need for increased generating capacity, and minimize the carbon footprint of the entire industry. 

Even before such wide reaching effects are possible, the information communicated by the individual components and systems can be used to conserve on a local level. Through internet communication and with the sensors already used in the system, a scheme of Fault Detection and Diagnosis (FDD) is not only possible but imminent. Experienced service mechanics are already able to look at various aspects of system performance and remotely diagnose, or at least narrow down, the possible problems in a system. In some cases, the system may be tested, or even fixed, remotely. Even if that is not possible, by knowing what to expect when he arrives, the technician will be able to bring the parts or information needed to actually fix the system. Even this can conserve energy and fuel in the form of fewer trips to the jobsite and parts distributor.

Future

There are certainly new technologies on the horizon, but commercialization and widespread use may be considered longer term: 20-30 years.

Much work is being done on thermo-acoustic refrigeration and cooling. The main attraction of thermo-acoustic technology is the reduction of moving parts and required maintenance. NASA is the main user and may continue to be for the foreseeable future. In thermo-acoustic cooling, a standing wave is induced in a closed tube by what amounts to a very high powered loudspeaker. The pressure pulses create warm and cold areas as the fluid is alternately compressed and allowed to expand. Experimental fluids include helium, as well as air. Varying the waveform can modify capacity, so theoretically, the power consumption is proportional to need.

As solar becomes a more important component of the energy supply, it may be used for refrigeration both directly and indirectly. Photo-voltaic cells can feed power into the electric grid, to be used by conventional technology. However, the heat generated by solar collectors can be used to directly power absorption refrigeration and air conditioning systems. The theory and use of absorption refrigeration dates to at least 1810 by John Leslie. Some materials, such as sulfuric acid, lithium bromide and ammonia, absorb heat when allowed to combine with water. Heat can be added to the resultant mixture to drive off the absorbed material which can later be allowed to re-absorb. In its simplest form this intermittent cycle can be used in various sized systems, for local cooling. Examples have been in use in the United States and Australia, as well as other locations, for decades. As with all solar technology, not all locations are appropriate.

Looking back, mechanical vapor compression refrigeration has been the backbone of the cooling industry and is likely to remain the predominant means for the next couple of decades. While new technologies are being developed now, commercialization may be longer term.

The present and short term will be based on improvements in efficiency, use of on-board diagnostics, communications and interfacing with the smart grid. All of which are present in products available today.